Condensation, ventilation and rooflights
Surface condensation on a rooflight is a whole-house ventilation problem showing up at the coldest point in the building. The glass is the messenger. Every kilogram of water a household puts into the air has to leave the building through moving air, and if it does not leave, it accumulates until the indoor air is humid enough that the coldest surface available drops below its dew point. This page is about the air side of that equation: how much water a dwelling generates, how much air it takes to carry it away, what the ventilation strategies are and how each one behaves once there is glass in the roof. The physics of horizontal glazing is covered on do flat rooflights cause condensation, the edge of the pane on warm-edge spacers and where condensation starts, and the thermal background on the energy efficient rooflights hub.
The moisture balance that decides everything downstream
A dwelling is a box with water going in and water coming out. Water goes in from the occupants and their activities. Water comes out almost entirely in the air that leaves the building, whether through a fan, an open window, a background ventilator or an unintended gap. A small amount is absorbed and released by furnishings and finishes, which buffers short spikes and changes nothing over a week.
If generation exceeds removal, the indoor humidity climbs until it settles at a new higher level. That level is a property of the whole house, not of the room the water was produced in, because moisture-laden air moves between rooms freely through doors, stairwells and gaps in the construction. A rooflight in a hallway can run wet because somebody dries washing in a bedroom two doors away.
How much water a household puts into the air in a day
The quantities are larger than people expect, and they are reasonably consistent between households.
| Source | Typical water released |
|---|---|
| Two adults breathing and perspiring over 24 hours | 1.5 to 2 litres |
| Cooking for a family across a day | 2 to 3 litres |
| Bathing and showering, per person per day | 0.2 to 0.5 litres |
| Washing up by hand | 0.5 litres |
| One load of washing dried indoors on an airer | 2 to 3 litres |
| A vented tumble dryer discharging into the room instead of outside | 2 litres or more per load |
| Unflued portable gas or paraffin heating | Roughly a litre for every litre of fuel burned |
A family of four with a washing load drying indoors is putting something like 10 to 15 litres of water into the air every day. That is a bucket. It has to go somewhere, and in a house where nothing is deliberately ventilating, the only place it can go is into the surfaces.
Moisture excess, and the number that drives the problem
Relative humidity is a poor way to think about this, because it changes with temperature even when no water has been added or removed. The useful quantity is the mass of water carried per kilogram of dry air, written in grams per kilogram.
What matters is not the indoor figure on its own but the difference between indoors and outdoors, called the moisture excess. That difference is produced entirely by what happens inside the building and is removed entirely by ventilation. Work it back: air holds about 1.2 kilograms per cubic metre, so a moisture excess of 3 grams per kilogram means each cubic metre of air leaving the house carries about 3.6 grams of water away with it. Removing 10 litres a day at that excess requires around 2,800 cubic metres of air, which is 116 cubic metres an hour, or about 32 litres per second running continuously. That figure is not a coincidence: it is very close to what the ventilation guidance asks a family home to achieve.
Dew point against surface temperature
Condensation forms when a surface is colder than the dew point of the air touching it. At a room temperature of 20 degrees the dew point moves with humidity as follows.
| Indoor relative humidity at 20 degrees | Dew point | What that means for the glass |
|---|---|---|
| 40 per cent | 6.0 degrees | A good modern unit stays clear on virtually every night of the year |
| 50 per cent | 9.3 degrees | Clear except at the glass edge on the coldest nights |
| 55 per cent | 10.7 degrees | An edge band on frosty mornings, drying by mid-morning |
| 60 per cent | 12.0 degrees | Regular edge condensation through winter, and the reveal corners at risk |
| 65 per cent | 13.2 degrees | Water across much of the pane on cold mornings, mould likely at junctions |
| 70 per cent | 14.4 degrees | Running condensation, and dampness that no glazing upgrade will cure |
The step from 50 to 65 per cent moves the dew point by nearly four degrees. Four degrees is more than the entire improvement a warm-edge spacer delivers at the glass edge, and roughly what an upgrade from double to triple glazing gains on the inner surface. Reducing humidity is the larger lever, and it is the cheaper one.
Air change rate, and the three ways it gets written down
Ventilation is quoted in three different units and confusion between them is common.
Air changes per hour, written ach, is the volume of the space replaced per hour. Litres per second is an absolute flow rate and is how fans and ventilators are rated. Litres per second per square metre of floor area is how a whole-dwelling requirement is normally set, because it scales with the size of the home rather than its shape. To convert, multiply litres per second by 3.6 to get cubic metres an hour, then divide by the room volume for air changes per hour. A background rate of about 0.5 ach across a dwelling is the traditional rule of thumb for moisture control, and a purge is ten to twenty times that for a few minutes.
What the guidance asks a dwelling to achieve
The ventilation part of the Building Regulations sets a whole-dwelling rate that rises with the number of bedrooms, from roughly 19 litres per second for a one bedroom home to over 40 for a five bedroom one, and never less than 0.3 litres per second for every square metre of internal floor area. That rate is what carries the daily bucket of water out.
It also sets purge ventilation, which for a habitable room is an openable area of at least one twentieth of the floor area, and extract at source in the wet rooms. Adding a rooflight to a habitable room engages both: a unit with an opening sash contributes to the purge requirement, and one with a ventilation flap in the head contributes to background ventilation. A fixed unit contributes daylight and nothing to either, which is worth knowing before choosing one for a room that was already marginal.
Extract at source, and the rates that apply room by room
Removing water where it is produced is always more efficient than diluting it through the whole house afterwards, because the air being thrown away is the wettest air in the building.
- A kitchen needs 30 litres per second if the extract sits over the hob, or 60 litres per second if it is elsewhere in the room.
- A bathroom or shower room needs 15 litres per second.
- A utility room needs 30 litres per second.
- A separate WC needs 6 litres per second.
Those are intermittent rates, running while the room is in use and for a period afterwards. Continuous running systems use lower figures with a boost. The common failure is not the absence of a fan but a fan that no longer moves its rated air: ducting off its spigot in a ceiling void, a sharp bend within 300mm of the outlet, 100mm flexible hose serving a unit designed for 125mm rigid, or a grille clogged with dust and paint. A fan rated at 15 litres per second on the box can be delivering 4 in service.
Background ventilators, equivalent area, and the vent nobody opens
Background ventilation is the small, steady, controllable air exchange that runs all the time, and it is the part of the system that has quietly disappeared from most houses.
Background ventilators are sized by equivalent area in square millimetres, which is not the same as the physical hole: it is the area of a sharp-edged orifice that would pass the same air at the same pressure difference, and it accounts for the resistance of the grille, the insect mesh and the airflow path. Current guidance sets a required equivalent area room by room, and for a habitable room in a reasonably airtight dwelling that commonly falls in the region of 5,000 to 8,000 square millimetres. Ventilators are meant to sit high in the room, typically at least 1.7 metres above floor level, so the incoming cool air mixes before it reaches anyone sitting down. A roof window ventilation flap sits at the head of the unit, which is the highest point in the room and thermally the right place for it.
The universal problem is that these are closable and they get closed in November. A ventilator that is shut is a ventilator that is not there, and the humidity climb through a winter is gradual enough that nobody connects the two. Humidity-sensitive ventilators, which open and close on a hygroscopic element with no power and no controls, solve this by taking the decision away from the occupant.

Four ventilation strategies, and how a rooflight behaves in each
| Strategy | How it works | What it means for a rooflight |
|---|---|---|
| Intermittent extract with background ventilators | Fans in the wet rooms, trickle ventilators in every room, the rest by natural pressure | The commonest arrangement and the most dependent on occupants. A vent flap in the unit is a real part of the system |
| Passive stack ventilation | Vertical ducts from wet rooms to ridge terminals, driven by buoyancy and wind | A rooflight opening at high level competes with the stack for the same driving pressure, so the two want designing together |
| Continuous mechanical extract | A low-rate fan running permanently with boost, either a central unit or one per wet room | The steadiest humidity control. Background ventilators are still needed as the air inlets, including the flap in the unit |
| Mechanical ventilation with heat recovery | Balanced supply and extract through a heat exchanger, in an airtight dwelling | Trickle ventilators are deliberately omitted, so a rooflight in that house should be specified without a background flap and used for purge only |
| Positive input ventilation from the loft | A unit in the roof space gently pressurises the house with filtered air | The loft has to stay a loft. Converting it removes the plenum the unit was using |
Getting this wrong in either direction causes problems. A trickle flap fitted into a house with heat recovery short-circuits the balanced system. A unit with no flap fitted into a naturally ventilated Victorian terrace removes a background path the room needed.
Airtightness, and why a tighter house makes the glass wetter
Air permeability is measured by pressurising the dwelling to 50 pascals and recording the leakage in cubic metres per hour per square metre of envelope. An untouched Victorian terrace with suspended floors and open chimneys might be 15 to 25. A well-built current house is 3 to 5. Deep retrofit and high-performance construction go below 1.
Here is the part that catches people out. The leaky house ventilated itself accidentally, all winter, at enormous heating cost, and its rooflights ran clear because the moisture excess never had a chance to build. Improve the envelope without installing the deliberate ventilation that is supposed to accompany it and you have removed the removal mechanism while leaving the generation untouched. The moisture excess rises, the dew point rises with it, and the coldest surface in the house, which is now the glass overhead, becomes the place it shows. It reads as a fault in the new rooflight. It is the arithmetic of the whole dwelling arriving at its weakest point.
What has been sealed up since the house was built
Working through the list on a survey is usually more productive than anything else, because each item removed a path that used to work.
- Chimneys capped or blocked during a refit, each of which was drawing several litres per second continuously.
- Replacement windows fitted without trickle ventilators, common on work carried out through the 1990s and 2000s.
- Airbricks blocked by a raised patio, a rendered plinth, or a fitted kitchen unit built across the inside face.
- Suspended timber floors overlaid with a solid screed or a membrane during a kitchen refit.
- Draught proofing to doors and letterplates, and loft hatches sealed and insulated.
- An extract fan removed and plastered over during a bathroom refit and never reinstated.
- Internal doors replaced without the 10mm undercut that lets air move between rooms.
Restoring two or three of those often does more for a wet rooflight than a glazing upgrade would, and costs a fraction of it.
Purge, and why ten minutes beats an hour
Purge ventilation is a short, large exchange rather than a small continuous one, and it is the most efficient moisture removal available in a house because of a property of building fabric that is easy to overlook.
Air has almost no heat capacity. The plaster, the floor, the furniture and the masonry hold hundreds of times more heat than the air in the room. Open a rooflight and a window fully for ten minutes on a cold morning and the air is completely exchanged, taking its water with it, while the surfaces barely cool. Close up, and the fabric reheats the fresh air within minutes at very little energy cost. Leaving a single window on the latch for four hours does the opposite: it exchanges less air in total and it chills the surfaces, which is both colder and less effective. The stack effect makes a rooflight the best purge opening in any room, because warm wet air is already collected at the ceiling waiting to leave.
The heat cost of ventilating, and why it is smaller than it feels
Householders resist background ventilation because it feels like throwing heat away. The arithmetic puts it in proportion.
Heating outside air to room temperature costs about 0.33 watt hours for every cubic metre and every degree of temperature rise. A 90 cubic metre house at half an air change per hour is 45 cubic metres an hour. On a January day 15 degrees colder outside than in, that is 0.33 multiplied by 45 multiplied by 15, or around 223 watts. Meaningful, and considerably less than the cost of running a dehumidifier and a heater to fight the consequences of not ventilating, and far less than the cost of mould at the reveal junctions. Uncontrolled leakage is the expensive version of the same thing, because it is largest on the windiest, coldest nights when heating is already working hardest.
Loft conversions, and the ventilation that has to be redesigned
A loft conversion changes the ventilation of the whole house, not just the new room, and rooflights are usually the only openings the new space gets.
Three things shift at once. The stairwell now runs from the ground floor to the ridge, so the stack pressure across the building increases and warm wet air from the kitchen and bathrooms is drawn upward far more strongly than before. The new room is at the top of that column, so it receives the most humid air in the house. And any positive input ventilation unit that was sitting in the roof space has lost its plenum and needs relocating or replacing with a different system.
What follows is that a loft rooflight needs an opening sash rather than a fixed pane wherever it is the only ventilation the room has, and that on the trussed estates at Quedgeley, Brockworth and Bishops Cleeve, where the narrow 550mm wide units are what fits between trusses, two openings in adjacent bays give both the purge area and the cross-flow that one unit cannot. Where the unit sits high over a stairwell and no handle can be reached, a rain-sensing electric opener with a humidity sensor is the arrangement that gets used, described on electric rooflight installation.
Severn Vale mist, and why cold saturated air still dries a house
Gloucester, Longford, Tewkesbury and the vale villages sit low beside a tidal river on ground that holds mist, and outdoor relative humidity through a still winter night is frequently at or near 100 per cent. The reasonable conclusion is that opening anything will make the house wetter. That conclusion is wrong, and the reason is the difference between relative and absolute humidity.
Saturated outside air at 4 degrees carries about 5 grams of water per kilogram, because cold air cannot hold much. Indoor air at 20 degrees and 60 per cent relative humidity carries about 8.8 grams per kilogram. Bring the outside air in and warm it to 20 degrees and its relative humidity falls to about 34 per cent, because its capacity has tripled while its water content has not changed. It arrives thirsty. Even river mist at saturation is drier in absolute terms than the air in a Severn Vale kitchen, and ventilating with it removes water from the house.
The exception is a mild damp spell, when outside air at 14 degrees and 95 per cent carries around 9.5 grams per kilogram and ventilating gains nothing. Those are also the days when surfaces are warm and condensation is not forming, so the strategy holds through the season that matters.
Reading the house before changing the glass
A digital thermometer and hygrometer costs very little and settles most of these arguments in a fortnight. Leave one in the room with the rooflight and a second one outside in the shade, and record both morning and evening.
What the readings tell you: indoor relative humidity consistently above 60 per cent at 20 degrees means the moisture balance is the problem and no glazing specification will fix it. Indoor humidity at 45 to 55 per cent with condensation still forming means the surface temperature is the problem, which points at the glass edge, the spacer, the frame or the insulation continuity at the reveal. A large moisture excess against the outdoor reading points at generation and extraction. A small excess with high indoor humidity means the outside air is genuinely wet and the timing of purge matters more than its duration.
Where the water is inside the sealed unit rather than on it, none of the above applies and the unit has reached the end of its life, which is set out on replacing a failed or misted rooflight. Where the damp is in the plaster at the reveal corners rather than on the glass, it is a junction temperature question covered on thermal bridging at the rooflight perimeter, and where warm air is getting into the construction itself the answer sits with vapour control layers sealed to the frame. Send photographs and a fortnight of readings to info@severnskylightsgloucester.co.uk and the reply will say which of the three it is.
Next on this subject.
- Guide U-values and glazing specification A U-value is the rate at which heat crosses one square metre of a finished rooflight for every degree of…
- Guide Solar gain, overheating and shading Overhead glazing collects far more solar energy in July than in January, and the ratio is not close. A rooflight…
- Guide Triple glazing in a rooflight and when it pays Triple glazing in a roof is worth more than triple glazing in a wall, and for a reason that has…
- Guide Warm-edge spacers and where condensation starts Watch any rooflight through a cold week and the water always arrives in the same place first: a band following…
- Guide Low-emissivity coatings and argon fills Roughly three quarters of the heat crossing an uncoated sealed unit travels as infrared radiation from the warm inner pane…
- Guide Thermal bridging at the rooflight perimeter The glass in a modern rooflight is usually the best-performing part of the installation, and the 300mm of construction around…